Method · When the Spinning Stops
How this was made
The data, the rules, the model and the limits behind the film. Every figure on this page is generated from the frozen evidence pack, so it cannot drift from what the film shows.
- Pack
- how-much-fast-reserve v1
- Frozen
- 2026-09-28
How to read the labels
Every figure in the film carries one of these labels.
- observed
- Measured in the source data and shown as it was recorded.
- published
- A figure stated by a named authority, quoted with its source.
- calculated
- Arithmetic on observed data: counts, shares, medians. The method page gives the rule.
- modelled
- Output of our model. It shows a mechanism or a design case, not a measurement.
- hypothetical
- A what-if: what the data would look like under a rule nobody has applied.
- illustrative
- A picture of the idea. Nothing is read off it.
Terms
| Film word | Technical name | Definition | Taught in |
|---|---|---|---|
| frequency | system frequency | How fast every generator in the Nordic grid turns, all in step. 50 Hz is normal. | Fifty |
| trip | loss of generation | A power plant or import link disconnecting without warning. | A trip |
| lowest point | nadir | How far the frequency falls before the grid catches it. | A trip |
| floor | frequency limit after the reference incident | 49.0 Hz: the lowest the operators allow after the largest trip. Below 48.8 Hz, customers are disconnected automatically. | A trip |
| spinning mass | inertia; kinetic energy, GWs | Energy stored in the turning generators, measured in GWs. The more there is, the slower the fall. | Inside the hour |
| slower reserve | FCR-D | Plants that ramp up over several seconds once the frequency drops below 49.9 Hz. | Inside the hour |
| light hour | low-inertia hour | An hour with less spinning mass, usually windy or sunny with few large thermal plants running. Below 150 GWs in the operators' terms. | Fewer wheels |
| largest trip | reference incident | The biggest single loss the grid is designed for: 1,450 MW. | Fewer wheels |
| fast reserve | Fast Frequency Reserve, FFR | Reserve that switches on within about a second, at 49.7, 49.6 or 49.5 Hz. | Fewer wheels |
The decision
Question: How much fast reserve should the grid hold when there is less spinning mass to hold it up?
A year of the Nordic grid at ten readings a second: when a power plant drops out, how far the frequency falls depends on how much mass is spinning that hour. In light hours, a few hundred MW of fast reserve does what tens of GWs of extra spinning mass would. Fingrid open data and the Nordic operators' published figures; frozen and labelled.
What we claim, and what we do not
- Claim: in a light hour, a few hundred MW that react within a second do what tens of GWs of extra spinning mass would. That comparison is the operators' published figures, not our model.
- Observed: in 2025-08 to 2026-07 we found 19 trips; the deepest reached 49.651 Hz, and nothing fell below 49.6 Hz. The grid held every time.
- Not claimed: that the grid is unsafe; that any real event breached 49.0 Hz; which unit tripped on any day; a forecast of future spinning mass.
- The trips cluster in the months with the least spinning mass. With this few trips, we do not claim the grid trips more in summer.
Data sources
| Source | Licence | Used for |
|---|---|---|
| Fingrid open data, Frequency – historical data (dataset 339) · https://data.fingrid.fi/en/datasets/339 | CC BY 4.0 | Every frequency event and the featured trace |
| Fingrid open data, Kinetic energy of the Nordic power system – real time data (dataset 260) · https://data.fingrid.fi/en/datasets/260 | CC BY 4.0 | The spinning mass of every hour; the mass at each event |
| Fingrid open data, Fast Frequency Reserve FFR, procured volume (dataset 276) · https://data.fingrid.fi/en/datasets/276 | CC BY 4.0 | Which hours Fingrid bought fast reserve in, and how much |
| Nordic TSOs, Requirements for minimum inertia in the Nordic power system, 28 August 2025 · https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/SOC%20documents/Nordic/2025/2025_-_Requirements_for_minimum_inertia_in_the_Nordic_power_system.pdf | cited | The floor, the largest trip, the design points, the yearly counts |
| Nordic TSOs, FFR Design of Requirements, external document v1.0 · https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/SOC%20documents/Nordic/2024/1c_-_FFR_Design_Requirements_v1.0_-_external_document.pdf | cited | About 300 MW of fast reserve at 100 GWs |
| Ørum et al. 2017, Future System Inertia 2, p. 101, as cited in Energinet's FFR methodology · https://www.energinet.dk/media/iiolq115/method-for-technical-requirements-for-and-new-procurement-of-ffr.pdf | cited | About 20 GWs of extra mass per 0.1 Hz |
| Fingrid, Fast Frequency Reserve FFR · https://www.fingrid.fi/en/electricity-market/reserves/reserve-products/fast-frequency-reserve-ffr/ | cited | The fast reserve product: activation points and times |
Window: 2025-08 to 2026-07, 8,760 hours. 314,629,395 frequency samples at 10 a second; 4 of 12 months have missing samples, held at the last good value. Kinetic energy covers 79 months since 2020, for the yearly counts.
Time zones: the 10 Hz archive is in Finnish local time (29 March 2026 has no 03:00 hour), and the API datasets are UTC. Every event carries both, and events are paired with their hour on UTC.
| Month | Samples | Missing |
|---|---|---|
| 2025-08 | 26,461,939 | 0% |
| 2025-09 | 25,805,260 | 0% |
| 2025-10 | 26,758,773 | 0% |
| 2025-11 | 25,912,703 | 0% |
| 2025-12 | 26,776,824 | 0% |
| 2026-01 | 26,760,440 | 0% |
| 2026-02 | 24,177,012 | 0% |
| 2026-03 | 26,712,956 | 0% |
| 2026-04 | 25,873,169 | 0% |
| 2026-05 | 26,762,368 | 0% |
| 2026-06 | 25,869,543 | 0% |
| 2026-07 | 26,758,408 | 0% |
Pipeline and how to reproduce it
- scripts/fetch-fingrid.py pulls the keyed datasets (260 kinetic energy, 276 fast reserve) into a local cache, one file per month, in 10-day ranges because the API stops paging at 40,000 rows.
- scripts/scan-grid-events.py downloads each month's 10 Hz archive (keyless), filters it, and lists every sustained fall.
- scripts/freeze-grid-inertia.py classifies each fall by its shape, pairs it with its hour, counts the hours, and writes the evidence pack.
- src/lib/sim/grid-frequency.ts is the frequency model; grid-validation.ts checks it against the trips in the pack.
- src/lib/sim/grid-evidence.test.ts checks the pack against the published figures on every test run.
# Free key from https://data.fingrid.fi; kept in the environment, never in the repo
export FINGRID_API_KEY=...
python3 scripts/fetch-fingrid.py 260 2020-01 2026-07
python3 scripts/fetch-fingrid.py 276 2020-01 2026-07
python3 scripts/scan-grid-events.py 2025-08 2025-09 2025-10 2025-11 2025-12 2026-01 2026-02 2026-03 2026-04 2026-05 2026-06 2026-07 > scan.json
python3 scripts/freeze-grid-inertia.py --scan scan.json
npx vitest run src/lib/sim/grid-evidence.test.ts src/lib/sim/grid-validation.test.tsEvents: what counts as a trip
observedFilter: median over 9 samples (0.9 s); samples outside 49–51 Hz are gaps and read as 50 Hz. Why: the raw series has 1–2-sample spikes (one reads 48.86 Hz between two 50.07 Hz samples); a raw minimum would report near-misses that never happened.
Detector: fall of more than 100 mHz within 5 s, at least 2 min after the previous one; nadir is the minimum within 20 s. a fall within 20 s of the hour is a market-schedule step, not a trip, and is excluded from trip counts.
Times: `t` is the start of the 5 s window the fall is detected in; `onset` is where the fall begins (first sample 15 mHz below the pre-event mean, less 0.2 s). Both are Finnish local time, as in the archive; `onset_utc` is UTC.
The detector caught 33 sustained falls. Each is classified by its shape; the rule was checked by eye on the borderline traces. Only trips enter the trip counts. Every event stays in the pack with its class.
| Class | Rule | Events |
|---|---|---|
| Trip | falls at least 100 mHz below the pre-event level, bottoms out 2 s or more after onset, and is still at least 20% down 25–35 s later | 19 |
| Schedule step | within 20 s of the hour: a market-schedule step | 3 |
| Gap | missing samples around the event | 0 |
| Held-then-jump | a filtered step steeper than 0.6 Hz/s, which no real loss produces; the reading holds, then jumps | 2 |
| Shallow | less than 100 mHz below the pre-event level: a fall from a local peak | 4 |
| Snap-back | less than 20% of the fall remains 25–35 s later; a lost generator leaves the frequency low for minutes | 3 |
| Fast dip | bottoms out within 2 s: a fault-driven swing at the measuring point dominates the reading, so its depth is not the system's | 2 |
Loss size: loss ≈ 2 × kinetic energy × |mean slope over the first second| / 50 Hz. A lower bound: reserves and load relief already push back within that second, and the 0.9 s filter softens the first slope. Kinetic energy at an event: the latest dataset-260 value at or before the onset, at most 15 min old.
| Onset | Class | Before, Hz | Lowest, Hz | Depth, mHz | To lowest, s | Mass, GWs | Fast reserve, MW | Est. loss, MW |
|---|---|---|---|---|---|---|---|---|
| 2025-08-25 13:57:08.1 | Held-then-jump | 50.021 | 49.877 | -144 | 12.5 | 150.5 | 6.1 | 850 |
| 2025-09-03 20:37:54.5 | Shallow | 50.044 | 50.005 | -40 | 7.2 | 180.8 | 0.0 | 30 |
| 2025-09-09 09:26:21.1 | Shallow | 50.009 | 49.917 | -92 | 7.8 | 193.6 | 0.0 | 170 |
| 2025-09-15 09:53:09.8 | Held-then-jump | 49.969 | 49.865 | -104 | 0.7 | 151.0 | 0.0 | 750 |
| 2025-09-22 13:38:46.3 | Trip | 50.009 | 49.858 | -151 | 6.6 | 161.6 | 0.0 | 340 |
| 2025-09-24 12:18:03.8 | Trip | 49.998 | 49.843 | -156 | 9.5 | 178.3 | 0.0 | 70 |
| 2025-10-29 11:45:21.0 | Trip | 49.967 | 49.804 | -163 | 7.5 | 208.9 | 0.0 | 290 |
| 2025-10-29 15:12:15.9 | Trip | 49.958 | 49.779 | -178 | 7.2 | 215.2 | 0.0 | 400 |
| 2025-12-01 15:30:58.8 | Shallow | 50.002 | 49.950 | -52 | 8.6 | 232.4 | 0.0 | 30 |
| 2026-01-01 15:08:57.4 | Trip | 49.984 | 49.836 | -149 | 8.7 | 203.1 | 0.0 | 550 |
| 2026-02-22 09:49:02.6 | Trip | 49.976 | 49.807 | -169 | 12.3 | 204.8 | 0.0 | 520 |
| 2026-03-11 13:06:54.1 | Trip | 50.023 | 49.869 | -153 | 5.4 | 174.0 | 0.0 | 930 |
| 2026-03-17 22:32:51.8 | Trip | 50.016 | 49.868 | -148 | 15.9 | 185.1 | 0.0 | 270 |
| 2026-04-01 08:18:45.7 | Trip | 50.050 | 49.929 | -121 | 8.8 | 192.3 | 0.0 | 350 |
| 2026-04-05 18:23:23.9 | Snap-back | 50.015 | 49.807 | -209 | 1.7 | 148.0 | 0.0 | 940 |
| 2026-04-08 14:13:35.6 | Trip | 49.958 | 49.787 | -171 | 5.9 | 173.1 | 0.0 | 430 |
| 2026-04-13 04:23:07.5 | Trip | 49.989 | 49.774 | -215 | 8.6 | 185.9 | 0.0 | 450 |
| 2026-04-16 00:46:35.2 | Trip | 49.985 | 49.845 | -141 | 11.5 | 182.6 | 0.0 | 250 |
| 2026-05-08 13:34:01.5 | Snap-back | 50.011 | 49.880 | -131 | 1.2 | 152.9 | 0.0 | 680 |
| 2026-05-08 15:47:09.3 | Snap-back | 49.992 | 49.881 | -111 | 3.9 | 153.6 | 0.0 | 250 |
| 2026-05-11 12:15:36.4 | Trip | 49.946 | 49.819 | -127 | 13.0 | 168.2 | 0.0 | 410 |
| 2026-05-27 20:45:33.8 | Trip | 49.965 | 49.823 | -142 | 6.3 | 154.0 | 0.0 | 330 |
| 2026-06-01 17:44:06.5 | Trip | 49.952 | 49.651 | -302 | 5.5 | 169.6 | 0.0 | 1,090 |
| 2026-06-06 01:00:00.1 | Schedule step | 50.037 | 49.854 | -183 | 13.8 | 164.8 | 0.0 | 110 |
| 2026-06-07 11:07:17.2 | Trip | 49.973 | 49.817 | -156 | 5.5 | 125.0 | 24.4 | 350 |
| 2026-06-08 16:13:47.3 | Trip | 49.945 | 49.804 | -141 | 5.6 | 163.1 | 0.0 | 450 |
| 2026-06-11 13:08:48.5 | Trip | 50.000 | 49.814 | -187 | 5.3 | 158.9 | 0.0 | 560 |
| 2026-06-16 14:26:33.5 | Trip | 50.036 | 49.851 | -184 | 8.6 | 156.1 | 0.0 | 310 |
| 2026-06-21 16:38:15.0 | Fast dip | 50.070 | 49.885 | -185 | 1.3 | 131.4 | 23.9 | 810 |
| 2026-06-25 11:00:04.8 | Schedule step | 50.045 | 49.841 | -204 | 5.2 | 165.3 | 0.0 | 650 |
| 2026-07-07 16:50:40.8 | Shallow | 50.036 | 49.943 | -94 | 4.5 | 149.9 | 12.9 | 220 |
| 2026-07-12 22:00:01.0 | Schedule step | 50.034 | 49.844 | -190 | 4.3 | 167.9 | 0.0 | 600 |
| 2026-07-19 12:56:31.0 | Fast dip | 49.997 | 49.708 | -289 | 1.6 | 136.1 | 40.7 | 920 |
Hours and fast reserve
calculatedHourly means of the real-time estimate. The published KPIs use the operators' own pre-disturbance series, so small differences are expected. 2020's minimum is one outlying hour in March (58 GWs) in the real-time series; the published minimum is 135. The latest year is partial
| Year | Hours | Mean, GWs | Lowest, GWs | Below 150 (ours) | Below 150 (published) | Below 120 (ours) |
|---|---|---|---|---|---|---|
| 2020 | 8,771 | 190 | 58 | 229 | 243 | 1 |
| 2021 | 8,757 | 195 | 110 | 534 | 559 | 28 |
| 2022 | 8,745 | 193 | 138 | 82 | 88 | 0 |
| 2023 | 8,754 | 194 | 127 | 237 | 237 | 0 |
| 2024 | 8,753 | 194 | 131 | 334 | 339 | 0 |
| 2025 | 8,760 | 194 | 128 | 299 | — | 0 |
| 2026 | 5,088 | 187 | 120 | 689 | — | 1 |
| Month | Hours | Below 150 | Below 120 |
|---|---|---|---|
| 2024-08 | 744 | 24 | 0 |
| 2024-09 | 720 | 38 | 0 |
| 2024-10 | 743 | 9 | 0 |
| 2024-11 | 720 | 0 | 0 |
| 2024-12 | 728 | 0 | 0 |
| 2025-01 | 744 | 0 | 0 |
| 2025-02 | 672 | 0 | 0 |
| 2025-03 | 744 | 0 | 0 |
| 2025-04 | 720 | 8 | 0 |
| 2025-05 | 744 | 56 | 0 |
| 2025-06 | 720 | 46 | 0 |
| 2025-07 | 744 | 5 | 0 |
| 2025-08 | 744 | 65 | 0 |
| 2025-09 | 720 | 80 | 0 |
| 2025-10 | 744 | 39 | 0 |
| 2025-11 | 720 | 0 | 0 |
| 2025-12 | 744 | 0 | 0 |
| 2026-01 | 744 | 0 | 0 |
| 2026-02 | 672 | 0 | 0 |
| 2026-03 | 744 | 30 | 0 |
| 2026-04 | 720 | 75 | 0 |
| 2026-05 | 744 | 195 | 1 |
| 2026-06 | 720 | 205 | 0 |
| 2026-07 | 744 | 184 | 0 |
| Hours | Median mass, GWs | Trips | Trips per 1,000 hours | Median est. loss, MW | |
|---|---|---|---|---|---|
| April–September | 4,392 | 165.7 | 13 | 2.96 | 350 |
| October–March | 4,368 | 214.8 | 6 | 1.37 | 460 |
Fingrid's FFR procured in each clock hour against that hour's mean kinetic energy, in 20 GWs bands.
| GWs | Hours | Hours with reserve | Mean MW |
|---|---|---|---|
| 100–120 | 1 | 100% | 28.4 |
| 120–140 | 333 | 91% | 21.4 |
| 140–160 | 1,479 | 40% | 6.8 |
| 160–180 | 2,273 | 9% | 1.4 |
| 180–200 | 1,744 | 0% | 0.0 |
| 200–220 | 970 | 0% | 0.0 |
| 220–240 | 1,061 | 0% | 0.0 |
| 240–260 | 804 | 0% | 0.0 |
| 260–280 | 95 | 0% | 0.0 |
| GWs | Hours | Hours with reserve | Mean MW |
|---|---|---|---|
| 100–120 | 29 | 93% | 23.6 |
| 120–140 | 739 | 83% | 21.0 |
| 140–160 | 5,481 | 54% | 10.1 |
| 160–180 | 14,607 | 26% | 3.7 |
| 180–200 | 14,640 | 5% | 0.6 |
| 200–220 | 8,712 | 0% | 0.0 |
| 220–240 | 6,538 | 0% | 0.0 |
| 240–260 | 3,556 | 0% | 0.0 |
| 260–280 | 210 | 0% | 0.0 |
The model and its check
modelledOne-bus swing equation: the whole synchronous grid is one spinning mass. It draws the shape of a fall for the design case. It is never quoted as a figure in the film.
df/dt = f₀ · (−loss + slower reserve + fast reserve + load relief) / (2 · kinetic energy)| Parameter | Value |
|---|---|
| Slower reserve (FCR-D), full at 49.5 Hz, linear from 49.9 Hz | 1,450 MW |
| Its dead time | 0.75 s |
| Its first-order lag | 3.5 s |
| Load relief | 0.5 % per Hz of 40,000 MW |
| Fast reserve options (activation, full within) | 49.7 Hz / 1.3 s · 49.6 Hz / 1 s · 49.5 Hz / 0.7 s |
| Case | Published | Model |
|---|---|---|
| 150 GWs, 1,450 MW lost, no fast reserve | 49.00 Hz | 49.00 Hz |
| 100 GWs, 1,450 MW lost, 300 MW fast reserve at 49.6 Hz | 49.00 Hz | 49.05 Hz |
| Extra mass for 0.1 Hz at 80 GWs | 20 GWs | about 11 GWs: missed; that study used the pre-2024 reserve requirements |
Check against the 19 trips: each loss is backed out from the trip's first second at that hour's kinetic energy and pre-event frequency, and the model's lowest point compared with the measured one. Timing is right (median 7.2 s modelled against 7.5 s observed). Depth is a median 1.72× deeper than the real trips, because the design case leaves out the normal-operation reserve, part of the load relief and providers faster than the minimum. So the film draws the model only for the design case, labelled modelled, and never over an observed trip as a prediction.
| Detected | Mass, GWs | Backed-out loss, MW | Depth observed, mHz | Depth modelled, mHz | To lowest observed, s | To lowest modelled, s |
|---|---|---|---|---|---|---|
| 2025-09-22 13:38:43.7 | 161.6 | 341 | 151 | 270 | 6.6 | 7.3 |
| 2025-09-24 12:18:03.5 | 178.3 | 72 | 155 | 123 | 9.5 | 16.8 |
| 2025-10-29 11:45:19.1 | 208.9 | 296 | 163 | 193 | 7.5 | 8.0 |
| 2025-10-29 15:12:12.8 | 215.2 | 409 | 179 | 233 | 7.2 | 7.4 |
| 2026-01-01 15:08:55.3 | 203.1 | 559 | 148 | 330 | 8.7 | 7.2 |
| 2026-02-22 09:49:00.8 | 204.8 | 522 | 169 | 305 | 12.3 | 7.2 |
| 2026-03-11 13:06:49.8 | 174.0 | 946 | 154 | 573 | 5.4 | 6.4 |
| 2026-03-17 22:32:51.2 | 185.1 | 270 | 148 | 233 | 15.9 | 8.9 |
| 2026-04-01 08:18:45.0 | 192.3 | 351 | 121 | 299 | 8.8 | 9.2 |
| 2026-04-08 14:13:32.3 | 173.1 | 435 | 171 | 265 | 5.9 | 6.3 |
| 2026-04-13 04:23:04.3 | 185.9 | 460 | 215 | 298 | 8.6 | 7.1 |
| 2026-04-16 00:46:34.4 | 182.6 | 252 | 140 | 197 | 11.5 | 8.1 |
| 2026-05-11 12:15:34.8 | 168.2 | 416 | 127 | 247 | 13.0 | 6.1 |
| 2026-05-27 20:45:31.0 | 154.0 | 338 | 142 | 233 | 6.3 | 6.2 |
| 2026-06-01 17:44:02.2 | 169.6 | 1,102 | 301 | 608 | 5.5 | 6.4 |
| 2026-06-07 11:07:13.8 | 125.0 | 357 | 156 | 269 | 5.5 | 5.5 |
| 2026-06-08 16:13:43.8 | 163.1 | 457 | 141 | 270 | 5.6 | 5.9 |
| 2026-06-11 13:08:44.7 | 158.9 | 568 | 186 | 379 | 5.3 | 6.3 |
| 2026-06-16 14:26:30.2 | 156.1 | 317 | 185 | 285 | 8.6 | 7.9 |
Figures in the film
| Figure | Kind | Note |
|---|---|---|
| 1 June 2026, 17:44 Finnish time: the frequency fell to 49.651 Hz in 5.5 s | observed | Fingrid 10 Hz frequency, median-filtered over 0.9 s. The hour held 169.6 GWs of kinetic energy and no fast reserve was bought. |
| 19 trips in a year; none fell below 49.6 Hz | calculated | 33 sustained falls, classified by shape; 19 are lost generation. |
| The largest trip at 194 and 100 GWs, with and without 300 MW of fast reserve | modelled | One-bus model fitted to the operators' design points; drawn as a shape, never quoted, and about 1.7× deeper than the real trips as a design case. |
| 873 hours below 150 GWs in the year; 584 of them in May–July 2026 | calculated | Hourly means of Fingrid's real-time estimate of Nordic kinetic energy. Our yearly counts are within 6% of the operators' published ones for 2020–2024. |
| Fast reserve bought in 91% of hours at 120–140 GWs, and in none above 200 GWs | calculated | Fingrid's procured volume per hour against that hour's kinetic energy. |
| Floor 49.0 Hz; largest trip 1,450 MW; about 300 MW of fast reserve at 100 GWs; about 20 GWs of mass per 0.1 Hz | published | Nordic TSOs 2025 and FFR design 2024; Ørum et al. 2017 via Energinet. |
| Wheels on a shaft, a plant that trips, a dial against the floor | illustrative | The dial follows the modelled trip to scale; the wheels' slow-down is exaggerated. |
Method in one paragraph
Directed film over one frozen evidence pack. Fingrid's 10 Hz frequency archive for August 2025 – July 2026 is median-filtered over 0.9 s and scanned for falls of more than 100 mHz within 5 s; each fall is classified by its shape, and 19 of 33 are trips. Each event is paired on UTC with that hour's kinetic energy and fast-reserve purchase. Hours are clock-hour means of Fingrid's real-time kinetic-energy estimate. Published thresholds are quoted from the Nordic operators. A one-bus frequency model fitted to the operators' design points draws the design-case curves and drives the illustration's dial; it is never quoted as a figure.
Sources
- Fingrid open data, Frequency – historical data (dataset 339), CC BY 4.0
- Fingrid open data, Kinetic energy of the Nordic power system (dataset 260), CC BY 4.0
- Fingrid open data, Fast Frequency Reserve FFR, procured volume (dataset 276), CC BY 4.0
- Nordic TSOs, Requirements for minimum inertia in the Nordic power system, 28 August 2025
- Frozen evidence pack v1 (how-much-fast-reserve), August 2025 – July 2026
Schema and download
The pack is one JSON file. Each top-level block below carries its own kind and source where it has one. Download it (122 KB).
| Block | Holds | Shape | Kind | Source |
|---|---|---|---|---|
| id | The story's slug. | text | ||
| version | Pack version; a re-freeze with a different shape bumps it. | number | ||
| generated | Date the pack was frozen. | text | ||
| status | What the pack is complete for. | text | ||
| sources | Every dataset and report, with its link and licence. | object, 7 fields | ||
| method | Every rule the pipeline applied, in words: filter, detector, classes, pairing, loss estimate. | object, 10 fields | ||
| coverage | Samples per month and the share missing. | object, 7 fields | observed | fingrid-339 |
| events | All sustained falls with their class, pairing and estimated loss, and a summary by class. | object, 5 fields | observed | fingrid-339 |
| pairing | Trips against their hour's spinning mass, by half-year. | object, 8 fields | calculated | fingrid-339, fingrid-260 |
| featured_event | The trip the film opens on, with its 10 Hz trace (raw and filtered). | object, 4 fields | observed | fingrid-339 |
| hours | Every hour of the window: its mean kinetic energy, and the fast reserve bought where any was. | object, 5 fields | observed | fingrid-260, fingrid-276 |
| years | Hours below 150 and 120 GWs by year and by month, ours and published, and fast reserve bought per year. | object, 7 fields | calculated | fingrid-260 |
| ffr_by_kinetic | Share of hours with fast reserve bought, by 20 GWs band of spinning mass. | object, 5 fields | calculated | fingrid-260, fingrid-276 |
| published | Figures quoted from the operators' reports, each with its source. | object, 2 fields | published | |
| limitations | What the evidence cannot say. | list of 7 |
Limitations
- Which unit tripped is not in the open data; events are unattributed, and their size is estimated from the first second of the fall.
- Event classes are a rule, not a label from the operator. The rule was checked by eye on the borderline traces; 19 trips is too few to settle the seasonal question.
- Frequency is measured at Finnish 400 kV substations; the Nordic system shares one frequency, but local oscillation is not separated.
- Kinetic energy is itself an operator estimate, updated every 15 minutes.
- Finland's FFR is one share of a Nordic need.
- Our model is one-bus and fitted to published design points; it draws shapes and is never quoted as a figure.
- No event in the window came near 49.0 Hz; the story is about margin, not a near-miss.
Reasoning: docs/decision-specs/grid-inertia-fast-reserve.md · pack: data/figures/how-much-fast-reserve.v1.json