Method · When the Spinning Stops

How this was made

The data, the rules, the model and the limits behind the film. Every figure on this page is generated from the frozen evidence pack, so it cannot drift from what the film shows.

Pack
how-much-fast-reserve v1
Frozen
2026-09-28

How to read the labels

Every figure in the film carries one of these labels.

observed
Measured in the source data and shown as it was recorded.
published
A figure stated by a named authority, quoted with its source.
calculated
Arithmetic on observed data: counts, shares, medians. The method page gives the rule.
modelled
Output of our model. It shows a mechanism or a design case, not a measurement.
hypothetical
A what-if: what the data would look like under a rule nobody has applied.
illustrative
A picture of the idea. Nothing is read off it.

Terms

Film wordTechnical nameDefinitionTaught in
frequencysystem frequencyHow fast every generator in the Nordic grid turns, all in step. 50 Hz is normal.Fifty
triploss of generationA power plant or import link disconnecting without warning.A trip
lowest pointnadirHow far the frequency falls before the grid catches it.A trip
floorfrequency limit after the reference incident49.0 Hz: the lowest the operators allow after the largest trip. Below 48.8 Hz, customers are disconnected automatically.A trip
spinning massinertia; kinetic energy, GWsEnergy stored in the turning generators, measured in GWs. The more there is, the slower the fall.Inside the hour
slower reserveFCR-DPlants that ramp up over several seconds once the frequency drops below 49.9 Hz.Inside the hour
light hourlow-inertia hourAn hour with less spinning mass, usually windy or sunny with few large thermal plants running. Below 150 GWs in the operators' terms.Fewer wheels
largest tripreference incidentThe biggest single loss the grid is designed for: 1,450 MW.Fewer wheels
fast reserveFast Frequency Reserve, FFRReserve that switches on within about a second, at 49.7, 49.6 or 49.5 Hz.Fewer wheels

The decision

Question: How much fast reserve should the grid hold when there is less spinning mass to hold it up?

A year of the Nordic grid at ten readings a second: when a power plant drops out, how far the frequency falls depends on how much mass is spinning that hour. In light hours, a few hundred MW of fast reserve does what tens of GWs of extra spinning mass would. Fingrid open data and the Nordic operators' published figures; frozen and labelled.

What we claim, and what we do not

  • Claim: in a light hour, a few hundred MW that react within a second do what tens of GWs of extra spinning mass would. That comparison is the operators' published figures, not our model.
  • Observed: in 2025-08 to 2026-07 we found 19 trips; the deepest reached 49.651 Hz, and nothing fell below 49.6 Hz. The grid held every time.
  • Not claimed: that the grid is unsafe; that any real event breached 49.0 Hz; which unit tripped on any day; a forecast of future spinning mass.
  • The trips cluster in the months with the least spinning mass. With this few trips, we do not claim the grid trips more in summer.

Data sources

SourceLicenceUsed for
Fingrid open data, Frequency – historical data (dataset 339) · https://data.fingrid.fi/en/datasets/339CC BY 4.0Every frequency event and the featured trace
Fingrid open data, Kinetic energy of the Nordic power system – real time data (dataset 260) · https://data.fingrid.fi/en/datasets/260CC BY 4.0The spinning mass of every hour; the mass at each event
Fingrid open data, Fast Frequency Reserve FFR, procured volume (dataset 276) · https://data.fingrid.fi/en/datasets/276CC BY 4.0Which hours Fingrid bought fast reserve in, and how much
Nordic TSOs, Requirements for minimum inertia in the Nordic power system, 28 August 2025 · https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/SOC%20documents/Nordic/2025/2025_-_Requirements_for_minimum_inertia_in_the_Nordic_power_system.pdfcitedThe floor, the largest trip, the design points, the yearly counts
Nordic TSOs, FFR Design of Requirements, external document v1.0 · https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/SOC%20documents/Nordic/2024/1c_-_FFR_Design_Requirements_v1.0_-_external_document.pdfcitedAbout 300 MW of fast reserve at 100 GWs
Ørum et al. 2017, Future System Inertia 2, p. 101, as cited in Energinet's FFR methodology · https://www.energinet.dk/media/iiolq115/method-for-technical-requirements-for-and-new-procurement-of-ffr.pdfcitedAbout 20 GWs of extra mass per 0.1 Hz
Fingrid, Fast Frequency Reserve FFR · https://www.fingrid.fi/en/electricity-market/reserves/reserve-products/fast-frequency-reserve-ffr/citedThe fast reserve product: activation points and times

Window: 2025-08 to 2026-07, 8,760 hours. 314,629,395 frequency samples at 10 a second; 4 of 12 months have missing samples, held at the last good value. Kinetic energy covers 79 months since 2020, for the yearly counts.

Time zones: the 10 Hz archive is in Finnish local time (29 March 2026 has no 03:00 hour), and the API datasets are UTC. Every event carries both, and events are paired with their hour on UTC.

Frequency samples by month
MonthSamplesMissing
2025-0826,461,9390%
2025-0925,805,2600%
2025-1026,758,7730%
2025-1125,912,7030%
2025-1226,776,8240%
2026-0126,760,4400%
2026-0224,177,0120%
2026-0326,712,9560%
2026-0425,873,1690%
2026-0526,762,3680%
2026-0625,869,5430%
2026-0726,758,4080%

Pipeline and how to reproduce it

  • scripts/fetch-fingrid.py pulls the keyed datasets (260 kinetic energy, 276 fast reserve) into a local cache, one file per month, in 10-day ranges because the API stops paging at 40,000 rows.
  • scripts/scan-grid-events.py downloads each month's 10 Hz archive (keyless), filters it, and lists every sustained fall.
  • scripts/freeze-grid-inertia.py classifies each fall by its shape, pairs it with its hour, counts the hours, and writes the evidence pack.
  • src/lib/sim/grid-frequency.ts is the frequency model; grid-validation.ts checks it against the trips in the pack.
  • src/lib/sim/grid-evidence.test.ts checks the pack against the published figures on every test run.
# Free key from https://data.fingrid.fi; kept in the environment, never in the repo
export FINGRID_API_KEY=...
python3 scripts/fetch-fingrid.py 260 2020-01 2026-07
python3 scripts/fetch-fingrid.py 276 2020-01 2026-07
python3 scripts/scan-grid-events.py 2025-08 2025-09 2025-10 2025-11 2025-12 2026-01 2026-02 2026-03 2026-04 2026-05 2026-06 2026-07 > scan.json
python3 scripts/freeze-grid-inertia.py --scan scan.json
npx vitest run src/lib/sim/grid-evidence.test.ts src/lib/sim/grid-validation.test.ts

Events: what counts as a trip

observed

Filter: median over 9 samples (0.9 s); samples outside 49–51 Hz are gaps and read as 50 Hz. Why: the raw series has 1–2-sample spikes (one reads 48.86 Hz between two 50.07 Hz samples); a raw minimum would report near-misses that never happened.

Detector: fall of more than 100 mHz within 5 s, at least 2 min after the previous one; nadir is the minimum within 20 s. a fall within 20 s of the hour is a market-schedule step, not a trip, and is excluded from trip counts.

Times: `t` is the start of the 5 s window the fall is detected in; `onset` is where the fall begins (first sample 15 mHz below the pre-event mean, less 0.2 s). Both are Finnish local time, as in the archive; `onset_utc` is UTC.

The detector caught 33 sustained falls. Each is classified by its shape; the rule was checked by eye on the borderline traces. Only trips enter the trip counts. Every event stays in the pack with its class.

Classes
ClassRuleEvents
Tripfalls at least 100 mHz below the pre-event level, bottoms out 2 s or more after onset, and is still at least 20% down 25–35 s later19
Schedule stepwithin 20 s of the hour: a market-schedule step3
Gapmissing samples around the event0
Held-then-jumpa filtered step steeper than 0.6 Hz/s, which no real loss produces; the reading holds, then jumps2
Shallowless than 100 mHz below the pre-event level: a fall from a local peak4
Snap-backless than 20% of the fall remains 25–35 s later; a lost generator leaves the frequency low for minutes3
Fast dipbottoms out within 2 s: a fault-driven swing at the measuring point dominates the reading, so its depth is not the system's2

Loss size: loss ≈ 2 × kinetic energy × |mean slope over the first second| / 50 Hz. A lower bound: reserves and load relief already push back within that second, and the 0.9 s filter softens the first slope. Kinetic energy at an event: the latest dataset-260 value at or before the onset, at most 15 min old.

All 33 events (onset in Finnish local time)
OnsetClassBefore, HzLowest, HzDepth, mHzTo lowest, sMass, GWsFast reserve, MWEst. loss, MW
2025-08-25 13:57:08.1Held-then-jump50.02149.877-14412.5150.56.1850
2025-09-03 20:37:54.5Shallow50.04450.005-407.2180.80.030
2025-09-09 09:26:21.1Shallow50.00949.917-927.8193.60.0170
2025-09-15 09:53:09.8Held-then-jump49.96949.865-1040.7151.00.0750
2025-09-22 13:38:46.3Trip50.00949.858-1516.6161.60.0340
2025-09-24 12:18:03.8Trip49.99849.843-1569.5178.30.070
2025-10-29 11:45:21.0Trip49.96749.804-1637.5208.90.0290
2025-10-29 15:12:15.9Trip49.95849.779-1787.2215.20.0400
2025-12-01 15:30:58.8Shallow50.00249.950-528.6232.40.030
2026-01-01 15:08:57.4Trip49.98449.836-1498.7203.10.0550
2026-02-22 09:49:02.6Trip49.97649.807-16912.3204.80.0520
2026-03-11 13:06:54.1Trip50.02349.869-1535.4174.00.0930
2026-03-17 22:32:51.8Trip50.01649.868-14815.9185.10.0270
2026-04-01 08:18:45.7Trip50.05049.929-1218.8192.30.0350
2026-04-05 18:23:23.9Snap-back50.01549.807-2091.7148.00.0940
2026-04-08 14:13:35.6Trip49.95849.787-1715.9173.10.0430
2026-04-13 04:23:07.5Trip49.98949.774-2158.6185.90.0450
2026-04-16 00:46:35.2Trip49.98549.845-14111.5182.60.0250
2026-05-08 13:34:01.5Snap-back50.01149.880-1311.2152.90.0680
2026-05-08 15:47:09.3Snap-back49.99249.881-1113.9153.60.0250
2026-05-11 12:15:36.4Trip49.94649.819-12713.0168.20.0410
2026-05-27 20:45:33.8Trip49.96549.823-1426.3154.00.0330
2026-06-01 17:44:06.5Trip49.95249.651-3025.5169.60.01,090
2026-06-06 01:00:00.1Schedule step50.03749.854-18313.8164.80.0110
2026-06-07 11:07:17.2Trip49.97349.817-1565.5125.024.4350
2026-06-08 16:13:47.3Trip49.94549.804-1415.6163.10.0450
2026-06-11 13:08:48.5Trip50.00049.814-1875.3158.90.0560
2026-06-16 14:26:33.5Trip50.03649.851-1848.6156.10.0310
2026-06-21 16:38:15.0Fast dip50.07049.885-1851.3131.423.9810
2026-06-25 11:00:04.8Schedule step50.04549.841-2045.2165.30.0650
2026-07-07 16:50:40.8Shallow50.03649.943-944.5149.912.9220
2026-07-12 22:00:01.0Schedule step50.03449.844-1904.3167.90.0600
2026-07-19 12:56:31.0Fast dip49.99749.708-2891.6136.140.7920

Hours and fast reserve

calculated

Hourly means of the real-time estimate. The published KPIs use the operators' own pre-disturbance series, so small differences are expected. 2020's minimum is one outlying hour in March (58 GWs) in the real-time series; the published minimum is 135. The latest year is partial

Hours below 150 GWs by year: ours from Fingrid's real-time estimate, and the operators' published count
YearHoursMean, GWsLowest, GWsBelow 150 (ours)Below 150 (published)Below 120 (ours)
20208,771190582292431
20218,75719511053455928
20228,74519313882880
20238,7541941272372370
20248,7531941313343390
20258,760194128299—0
20265,088187120689—1
Hours below 150 GWs by month, the last 24 months: the same month two years apart is the fairest comparison, because light hours are seasonal
MonthHoursBelow 150Below 120
2024-08744240
2024-09720380
2024-1074390
2024-1172000
2024-1272800
2025-0174400
2025-0267200
2025-0374400
2025-0472080
2025-05744560
2025-06720460
2025-0774450
2025-08744650
2025-09720800
2025-10744390
2025-1172000
2025-1274400
2026-0174400
2026-0267200
2026-03744300
2026-04720750
2026-057441951
2026-067202050
2026-077441840
Half-years in the window
HoursMedian mass, GWsTripsTrips per 1,000 hoursMedian est. loss, MW
April–September4,392165.7132.96350
October–March4,368214.861.37460

Fingrid's FFR procured in each clock hour against that hour's mean kinetic energy, in 20 GWs bands.

Fast reserve bought, by the hour's spinning mass: the window
GWsHoursHours with reserveMean MW
100–1201100%28.4
120–14033391%21.4
140–1601,47940%6.8
160–1802,2739%1.4
180–2001,7440%0.0
200–2209700%0.0
220–2401,0610%0.0
240–2608040%0.0
260–280950%0.0
The same, since 2020
GWsHoursHours with reserveMean MW
100–1202993%23.6
120–14073983%21.0
140–1605,48154%10.1
160–18014,60726%3.7
180–20014,6405%0.6
200–2208,7120%0.0
220–2406,5380%0.0
240–2603,5560%0.0
260–2802100%0.0

The model and its check

modelled

One-bus swing equation: the whole synchronous grid is one spinning mass. It draws the shape of a fall for the design case. It is never quoted as a figure in the film.

df/dt = f₀ · (−loss + slower reserve + fast reserve + load relief) / (2 · kinetic energy)
Parameters
ParameterValue
Slower reserve (FCR-D), full at 49.5 Hz, linear from 49.9 Hz1,450 MW
Its dead time0.75 s
Its first-order lag3.5 s
Load relief0.5 % per Hz of 40,000 MW
Fast reserve options (activation, full within)49.7 Hz / 1.3 s · 49.6 Hz / 1 s · 49.5 Hz / 0.7 s
Calibration against the published design points
CasePublishedModel
150 GWs, 1,450 MW lost, no fast reserve49.00 Hz49.00 Hz
100 GWs, 1,450 MW lost, 300 MW fast reserve at 49.6 Hz49.00 Hz49.05 Hz
Extra mass for 0.1 Hz at 80 GWs20 GWsabout 11 GWs: missed; that study used the pre-2024 reserve requirements

Check against the 19 trips: each loss is backed out from the trip's first second at that hour's kinetic energy and pre-event frequency, and the model's lowest point compared with the measured one. Timing is right (median 7.2 s modelled against 7.5 s observed). Depth is a median 1.72× deeper than the real trips, because the design case leaves out the normal-operation reserve, part of the load relief and providers faster than the minimum. So the film draws the model only for the design case, labelled modelled, and never over an observed trip as a prediction.

Per trip
DetectedMass, GWsBacked-out loss, MWDepth observed, mHzDepth modelled, mHzTo lowest observed, sTo lowest modelled, s
2025-09-22 13:38:43.7161.63411512706.67.3
2025-09-24 12:18:03.5178.3721551239.516.8
2025-10-29 11:45:19.1208.92961631937.58.0
2025-10-29 15:12:12.8215.24091792337.27.4
2026-01-01 15:08:55.3203.15591483308.77.2
2026-02-22 09:49:00.8204.852216930512.37.2
2026-03-11 13:06:49.8174.09461545735.46.4
2026-03-17 22:32:51.2185.127014823315.98.9
2026-04-01 08:18:45.0192.33511212998.89.2
2026-04-08 14:13:32.3173.14351712655.96.3
2026-04-13 04:23:04.3185.94602152988.67.1
2026-04-16 00:46:34.4182.625214019711.58.1
2026-05-11 12:15:34.8168.241612724713.06.1
2026-05-27 20:45:31.0154.03381422336.36.2
2026-06-01 17:44:02.2169.61,1023016085.56.4
2026-06-07 11:07:13.8125.03571562695.55.5
2026-06-08 16:13:43.8163.14571412705.65.9
2026-06-11 13:08:44.7158.95681863795.36.3
2026-06-16 14:26:30.2156.13171852858.67.9

Figures in the film

FigureKindNote
1 June 2026, 17:44 Finnish time: the frequency fell to 49.651 Hz in 5.5 sobservedFingrid 10 Hz frequency, median-filtered over 0.9 s. The hour held 169.6 GWs of kinetic energy and no fast reserve was bought.
19 trips in a year; none fell below 49.6 Hzcalculated33 sustained falls, classified by shape; 19 are lost generation.
The largest trip at 194 and 100 GWs, with and without 300 MW of fast reservemodelledOne-bus model fitted to the operators' design points; drawn as a shape, never quoted, and about 1.7× deeper than the real trips as a design case.
873 hours below 150 GWs in the year; 584 of them in May–July 2026calculatedHourly means of Fingrid's real-time estimate of Nordic kinetic energy. Our yearly counts are within 6% of the operators' published ones for 2020–2024.
Fast reserve bought in 91% of hours at 120–140 GWs, and in none above 200 GWscalculatedFingrid's procured volume per hour against that hour's kinetic energy.
Floor 49.0 Hz; largest trip 1,450 MW; about 300 MW of fast reserve at 100 GWs; about 20 GWs of mass per 0.1 HzpublishedNordic TSOs 2025 and FFR design 2024; Ørum et al. 2017 via Energinet.
Wheels on a shaft, a plant that trips, a dial against the floorillustrativeThe dial follows the modelled trip to scale; the wheels' slow-down is exaggerated.

Method in one paragraph

Directed film over one frozen evidence pack. Fingrid's 10 Hz frequency archive for August 2025 – July 2026 is median-filtered over 0.9 s and scanned for falls of more than 100 mHz within 5 s; each fall is classified by its shape, and 19 of 33 are trips. Each event is paired on UTC with that hour's kinetic energy and fast-reserve purchase. Hours are clock-hour means of Fingrid's real-time kinetic-energy estimate. Published thresholds are quoted from the Nordic operators. A one-bus frequency model fitted to the operators' design points draws the design-case curves and drives the illustration's dial; it is never quoted as a figure.

Sources

Schema and download

The pack is one JSON file. Each top-level block below carries its own kind and source where it has one. Download it (122 KB).

BlockHoldsShapeKindSource
idThe story's slug.text
versionPack version; a re-freeze with a different shape bumps it.number
generatedDate the pack was frozen.text
statusWhat the pack is complete for.text
sourcesEvery dataset and report, with its link and licence.object, 7 fields
methodEvery rule the pipeline applied, in words: filter, detector, classes, pairing, loss estimate.object, 10 fields
coverageSamples per month and the share missing.object, 7 fieldsobservedfingrid-339
eventsAll sustained falls with their class, pairing and estimated loss, and a summary by class.object, 5 fieldsobservedfingrid-339
pairingTrips against their hour's spinning mass, by half-year.object, 8 fieldscalculatedfingrid-339, fingrid-260
featured_eventThe trip the film opens on, with its 10 Hz trace (raw and filtered).object, 4 fieldsobservedfingrid-339
hoursEvery hour of the window: its mean kinetic energy, and the fast reserve bought where any was.object, 5 fieldsobservedfingrid-260, fingrid-276
yearsHours below 150 and 120 GWs by year and by month, ours and published, and fast reserve bought per year.object, 7 fieldscalculatedfingrid-260
ffr_by_kineticShare of hours with fast reserve bought, by 20 GWs band of spinning mass.object, 5 fieldscalculatedfingrid-260, fingrid-276
publishedFigures quoted from the operators' reports, each with its source.object, 2 fieldspublished
limitationsWhat the evidence cannot say.list of 7

Limitations

  • Which unit tripped is not in the open data; events are unattributed, and their size is estimated from the first second of the fall.
  • Event classes are a rule, not a label from the operator. The rule was checked by eye on the borderline traces; 19 trips is too few to settle the seasonal question.
  • Frequency is measured at Finnish 400 kV substations; the Nordic system shares one frequency, but local oscillation is not separated.
  • Kinetic energy is itself an operator estimate, updated every 15 minutes.
  • Finland's FFR is one share of a Nordic need.
  • Our model is one-bus and fitted to published design points; it draws shapes and is never quoted as a figure.
  • No event in the window came near 49.0 Hz; the story is about margin, not a near-miss.

Reasoning: docs/decision-specs/grid-inertia-fast-reserve.md · pack: data/figures/how-much-fast-reserve.v1.json