Skip to content
Skip to the decision

A year of the Nordic grid

When the spinning stops

How much fast reserve should the grid hold when there is less spinning mass to hold it up?

Illustration. The wheels' slow-down is exaggerated; the dial is to scale.

1 June 2026 · 17:43 Finnish time

observed

The grid turns at fifty.

Every generator in the Nordic grid turns in step,

Decision

published

Size fast reserve to the hour's spinning mass, and watch the light hours.

Fingrid already buys fast reserve by the hour: in 91% of the lightest hours, and none above 200 GWs. The open question is volume, because light hours are becoming more common.

The other way to hold the floor is to keep more mass spinning, with synchronous condensers or thermal plants kept online. By the operators' figures, lifting the lowest point by 0.1 Hz that way takes about 20 GWs more of it. About 300 MW of fast reserve holds the floor in their test case for a very light hour.

Light hours move with wind, water and sun from one year to the next, so one summer is not a forecast. It is a reason to size reserve to the hour rather than to the year.

Hours below 150 GWs: the operators' published counts, then ours from Fingrid's real-time estimate
PeriodHours below 150 GWsKind
202288published
2023237published
2024339published
2025299calculated
May–July 2026584calculated
  • The grid held every time: no event in Aug 2025 – Jul 2026 came near 49.0 Hz. This is a story about margin, not a near-miss.
  • We do not say which unit tripped on any day; the open data does not.
  • The modelled curves are a design case drawn as shapes. They are never a prediction of a real trip.
  • Finland's fast reserve is one share of a Nordic need.
Method, data and schema: every rule and all 33 events →

Source: Fingrid, data.fingrid.fi, licence CC BY 4.0. Published thresholds: Nordic TSOs 2025, FFR design 2024, Ørum et al. 2017. Not affiliated with, and not endorsed by, Fingrid or any Nordic operator.